Line 30: Line 30:
 
|- valign="top"
 
|- valign="top"
 
| 2020-02-23 || Incident 1: Several cable trays were damaged after a wind storm, the maximum wind gust speed reported by the MAGIC weather station during the storm was 157 km/h at ~8:00.|| To repair  || Several cable trays were repaired on 28.02.20|| [[File:IMG_20200303_122248.jpg|120px|thumb|center|]] || No
 
| 2020-02-23 || Incident 1: Several cable trays were damaged after a wind storm, the maximum wind gust speed reported by the MAGIC weather station during the storm was 157 km/h at ~8:00.|| To repair  || Several cable trays were repaired on 28.02.20|| [[File:IMG_20200303_122248.jpg|120px|thumb|center|]] || No
 +
 +
|- valign="top"
 +
| 2020-01-28 || There are drops of water from the humidifier in the wall of the IT container || To repair  || Schneider and LST Team  checked the humidifier and there was a loop in the drainage pipe. The loop was removed. The bottle was removed and it was broken. A new bottle was installed but the new holes are looking to the ceiling and they produce condensation on the ceiling. The humidifier cannot be connected in this situation because the water can wet the leak rope|| [[File:IMG-20200212-WA0006.jpg|120px|thumb|center|]] || No

Revision as of 11:46, 14 May 2020

Enter comments in reverse time order

Date What happened? Corrective measures Comments Documents Incident Closed?


2020-02-23 Incident 8: The camera shutter was broken after a wind storm, the maximum wind gust speed reported by the MAGIC weather station during the storm was 157 km/h at ~8:00. To repair LST people installed a temporal cover on 25.02.20. CIEMAT team checked the camera and they installed a better temporal cover on 26.02.20
IMG 20200225 141909.jpg
IMG 20200225 113146.jpg
No
2020-02-23 Incident 7: The camera access tower was opened after a wind storm, the maximum wind gust speed reported by the MAGIC weather station during the storm was 157 km/h at ~8:00. To check and to repair and to close LST people on site and Casana checked the platform. Everything was fine and they closed the platform from the control in the camera access tower on 25.02.20
DSC 0436.JPG
YES


2020-02-23 Incident 6: The camera maintenance room was moved after a wind storm, the maximum wind gust speed reported by the MAGIC weather station during the storm was 157 km/h at ~8:00. To relocate The room was relocated by Casana
IMG 20200225 094855.jpg
IMG 20200225 094830.jpg
Yes
2020-02-23 Incident 5: Several signs were removed and broken after a wind storm, the maximum wind gust speed reported by the MAGIC weather station during the storm was 157 km/h at ~8:00. To repair xxx No
2020-02-23 Incident 4: 2 piles from the fence were moved (the fence is not opened) after a wind storm, the maximum wind gust speed reported by the MAGIC weather station during the storm was 157 km/h at ~8:00. To repair xxx
IMG 20200225 102924.jpg
No
2020-02-23 Incident 3: A cover from the camera chiller was damaged after a wind storm, the maximum wind gust speed reported by the MAGIC weather station during the storm was 157 km/h at ~8:00. To repair The cover was installed on 25.02.20
IMG 20200225 151026.jpg
YES
2020-02-23 Incident 2: The roof of the chiller was damaged after a wind storm, the maximum wind gust speed reported by the MAGIC weather station during the storm was 157 km/h at ~8:00. To repair The roof was repaired by CASANA [ YES
2020-02-23 Incident 1: Several cable trays were damaged after a wind storm, the maximum wind gust speed reported by the MAGIC weather station during the storm was 157 km/h at ~8:00. To repair Several cable trays were repaired on 28.02.20
IMG 20200303 122248.jpg
No
2020-01-28 There are drops of water from the humidifier in the wall of the IT container To repair Schneider and LST Team checked the humidifier and there was a loop in the drainage pipe. The loop was removed. The bottle was removed and it was broken. A new bottle was installed but the new holes are looking to the ceiling and they produce condensation on the ceiling. The humidifier cannot be connected in this situation because the water can wet the leak rope
IMG-20200212-WA0006.jpg
No